To Make & Test the Working of Single Phase Preventer Using Contactor Control.

Experiment No.: 3

Experiment Name:

Making & testing the working of single phase preventer using contactor control.

Objective:

To make & test the working of single phase preventer using contactor control.

Theory:

Single phase preventer is used to protect theĀ induction motorĀ from single phasing fault. It is a very dangerousĀ faultĀ to theĀ electrical motorĀ and Which damages the motor stator winding rapidly. Generally single phasing is nothing but a motor runs when one of the supply is disconnected due toĀ open circuitĀ or improper contact in switch or other electrical equipment failure.

Normally, the motor runs with theĀ three phase supplyĀ and which takes balanceĀ currentĀ in each phase winding. Consider one of the fuse has blown. But the motor still in a rotating position which tries to rotates at the same speed. At that same time, the absenceĀ phase currentĀ will be shifted to the remaining liveĀ phases. Therefore, the current in the other phases increases up to 3 times its normal value instantly. This is called a single phasing fault.

The single phasing leads to anĀ unbalanced currentĀ in the motor stator. The component which is present in this unbalanced current calledĀ negative sequence component. This negative sequence component creates theĀ magnetic fluxĀ opposite to the mainĀ flux. This results in doubleĀ frequencyĀ currents to induce in the rotor to cause its heating.

Circuit Diagram:

Operation and Observation:

  1. When the system is normal, the START push button switch is pressed and released, then the main contactor coil, M gets energized and NO contact across the START is closed and at the same time the NO of single phase preventor is closed and NC is opened and the triple contact of the M contactor is closed. So the motor gets started.
  2. Now, when there is one or two phase are missing, then the closed NO contact of the single phase preventer gets opened and the opened NC contact will be closed. As a result the M contactor circuit is now opened and the contactor coil M gets de-energized and the contacts related this M, change there position and the motor stopped.
  3. Until the fault is cleared, the single phase preventer will prevent to make the circuit.

Apparatus Used:

Sl No.Name of the ApparatusSpecification QuantityMaker’s name
Ā 1.Single Phase PreventorĀ Ā 3 phase, 1NO, 1NC, 415 V, 50 Hz, DIN mount1Ā GiC
Ā 2.Contactor BlockĀ Ā 3 phase, 4 NO, 415 V, 63 A, 50 Hz, DIN mount1Ā Schneider
Ā 3.Induction MotorĀ Ā 3 phase, 1 HP, 415 V, 1440 rpm, Ā 1Ā Triple-D
Ā 4.Connecting CablesĀ 2.5 sq. mm, 1100 V grade, PVC insulated, FRLSĀ Ā as requiredMARUĀ 
Ā 5.Start and Stop SwitchĀ 1 NO, 1 NC Push Button SwitchĀ 2Ā  

Remarks: The circuit is made as per the diagram shown and the circuit is tested by creating single phase fault by swiching off any one phase at a time. The preventer works perfectly by disconnecting the motor from supply after occuring the fault.

Views: 112

2 thoughts on “To Make & Test the Working of Single Phase Preventer Using Contactor Control.”

Leave a Comment

Your email address will not be published. Required fields are marked *

Industrial PLC- Basic⚔ Hands-on Practical Training. Limited Seat- Enroll Now!

Close Welcome Bar
error

Enjoy this blog? Please spread the word :)