Calibration of Single Phase Electronic Energy Meter by Direct Loading

Experiment No.: 5

Experiment Name:

Calibrate single phase electronic energy meter by direct loading.

Objective:

To calibrate single phase electronic energy meter by direct loading using resistive load.

Theory:

An energy meter is an instrument used to measure electrical energy. It keeps a record of the total energy consumed in a circuit during a particular period. It is an integrating type of instrument. Calibration involves comparing the energy measured by an energy meter with a standard instrument. The standard chosen here is a wattmeter. Since the wattmeter measures only the power, it has to be multiplied with time to get the energy reading. The readings are then compared to find the error in the energy meter. Calibration can be done either by direct loading or phantom loading. In direct loading both the current and pressure coils are fed from the same supply at rated voltage. Energy meters of high rating when tested by direct loading would involve large amount of power. Such meters are thus tested using phantom loading, wherein the pressure coil is supplied from rated supply and current coil circuit from a separate low voltage supply.

Circuit Diagram:

Procedure:

  1. Connections are made as shown in the connection diagram.
  2. The supply is switched on, keeping the autotransformer in the minimum position.
  3. The autotransformer is then varied to get the rated voltage.
  4. The lamp load is then switched on and the ammeter reading adjusted for a small value of current.
  5. The corresponding readings of voltmeter, ammeter and wattmeter are noted down.
  6. The time for five impulse of the energy meter disc is also noted.
  7. The experiment is repeated in steps adding loads till the rated current of the energy meter is reached.
  8. The true energy and indicated energy is evaluated and the error found out.

Observation Table:

Sl. No.Voltmeter reading (V)Ammeter reading (A)Wattmeter reading (W)Time for 5 impulse, t1 (s)Time for 1 impulse, t2 (s)Indicated reading, IR (W.s)True reading, TR (W.s)Error (IR-TR) (W.s)% Error
  1.230 6.4 1440 3.97 0.794 1125  1143.36-18.36 -1.632 % 

Calculation:

Apparatus Used:

Sl. No.Name of the ApparatusSpecificationQuantityMakers name
 1.1-Ø & 3-Ø energy meter calibration study kit  230 V, 415 V1 M.E.W.
2. AC 1-Ø Static Energy meter240 V, 50 Hz, 5-30 A, 3200 imp/kWh, electronics 1KEI Electric and Electronics 
 3.Voltmeter 0-500 V, MI type 1Sushma 
 4.Ammeter 0-10 A 1Sushma 
 5.Wattmeter 150-300-600 V, 0-750-1500-3000 W, 5-10 A 1MECO-G 
6.1-Ø load box1.5 kW, resistive load1
7.Timer Smart phone used as timer 1 Samsung
 8.Connecting Cables Cu- conductor, 2.5 sq. mm., 1100 V grade, PVC, FRLC As required Maru

Result:

There is an error of -1.632% in the used energymeter.

2 thoughts on “Calibration of Single Phase Electronic Energy Meter by Direct Loading”

Leave a Comment

Your email address will not be published. Required fields are marked *

Free Mock Test Series on SSC JE Electrical. Test yourself Now!

X

You cannot copy content of this page

error

Enjoy this blog? Please spread the word :)